Label | Definition | Identifier | Serialisation |
---|---|---|---|
SynchronousMachine.operatingMode | Current mode of operation. | urn:uuid:1d3bb064-b765-4d06-992a-70f1ce3d0bd4 |
RDF/XML JSON-LD Turtle |
VsConverter.qPccControl | Kind of reactive power control. | urn:uuid:1f9a5f62-20b4-4b23-be8c-66117b6bf99e |
RDF/XML JSON-LD Turtle |
RegulatingControl.targetDeadband | This is a deadband used with discrete control to avoid excessive update of controls like tap changers and shunt compensator banks while regulating. The units of those appropriate for the mode. The attribute shall be a positive value or zero. If RegulatingControl.discrete is set to \"false\", the RegulatingControl.targetDeadband is to be ignored. Note that for instance, if the targetValue is 100 kV and the targetDeadband is 2 kV the range is from 99 to 101 kV. | urn:uuid:6583abb6-e1ea-4405-bc25-c4d4dfad175e |
RDF/XML JSON-LD Turtle |
ExternalNetworkInjection.p | Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions. | urn:uuid:067fdc37-ec07-4197-b329-d986eef6bd70 |
RDF/XML JSON-LD Turtle |
Switch.open | The attribute tells if the switch is considered open when used as input to topology processing. | urn:uuid:b281f8d6-257c-409f-900b-0aa3d39783c4 |
RDF/XML JSON-LD Turtle |
RegulatingControl.maxAllowedTargetValue | Maximum allowed target value (RegulatingControl.targetValue). | urn:uuid:f7d196c2-a20d-4cc6-a3e3-464474896028 |
RDF/XML JSON-LD Turtle |
ACDCConverter.targetPpcc | Real power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. | urn:uuid:504dcd38-ebb3-4422-af56-8e72f913c113 |
RDF/XML JSON-LD Turtle |
EquivalentInjection.regulationStatus | Specifies the regulation status of the EquivalentInjection. True is regulating. False is not regulating. | urn:uuid:7d6b8fd8-6483-4485-ae43-c70f7350a43c |
RDF/XML JSON-LD Turtle |
CurrentFlow.multiplier | No description defined. | urn:uuid:0cc39f5e-a2eb-451f-9177-583d1a6b8a37 |
RDF/XML JSON-LD Turtle |
CsConverter.targetAlpha | Target firing angle. It is converter’s control variable used in power flow. It is only applicable for rectifier if continuous tap changer control is used. Allowed values are within the range minAlpha<=targetAlpha<=maxAlpha. The attribute shall be a positive value. | urn:uuid:629f70ca-80fa-4b69-93ea-07c6df7eadee |
RDF/XML JSON-LD Turtle |
VsConverter.droop | Droop constant. The pu value is obtained as D [kV/MW] x Sb / Ubdc. The attribute shall be a positive value. | urn:uuid:228e6333-afac-438e-a6da-32c166c163e9 |
RDF/XML JSON-LD Turtle |
VsConverter.targetPWMfactor | Magnitude of pulse-modulation factor. The attribute shall be a positive value. | urn:uuid:083690bc-6aec-4c6a-80c4-aac3a1abf168 |
RDF/XML JSON-LD Turtle |
ShuntCompensator.sections | Shunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input. For LinearShuntConpensator the value shall be between zero and ShuntCompensator.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of non-integer values. For NonlinearShuntCompensator-s shall only be set to one of the NonlinearShuntCompenstorPoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPoint-s. | urn:uuid:a72689cb-9255-4ddd-bfc3-8938a3a4caf5 |
RDF/XML JSON-LD Turtle |
RegulatingControl.targetValue | The target value specified for case input. This value can be used for the target value without the use of schedules. The value has the units appropriate to the mode attribute. | urn:uuid:fac9e9ba-0243-4c55-9059-cd59e641be0c |
RDF/XML JSON-LD Turtle |
Switch.locked | If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
|
urn:uuid:6bf03f76-b5c5-4c63-84b6-eb588a4d01b4 |
RDF/XML JSON-LD Turtle |
ExternalNetworkInjection.referencePriority | Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on. | urn:uuid:ef6edeb3-a63d-4932-8066-6f6568be3833 |
RDF/XML JSON-LD Turtle |
VsConverter.targetUpcc | Voltage target in AC grid, at point of common coupling. The attribute shall be a positive value. | urn:uuid:9885198b-9671-41ee-8c75-d15ee4f13845 |
RDF/XML JSON-LD Turtle |
BatteryUnit.batteryState | The current state of the battery (charging, full, etc.). | urn:uuid:9eaf3aa3-04b9-450c-85e5-c410e10d3448 |
RDF/XML JSON-LD Turtle |
EquivalentInjection.p | Equivalent active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions. | urn:uuid:27be6d3d-5a79-437a-9e5c-ab0a98c5e9b1 |
RDF/XML JSON-LD Turtle |
ACDCConverter.targetUdc | Target value for DC voltage magnitude. The attribute shall be a positive value. | urn:uuid:cde58ebf-a94d-4164-bf3d-97036e74d990 |
RDF/XML JSON-LD Turtle |
RotatingMachine.q | Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. | urn:uuid:ad3e22a4-0b58-4e9b-a795-b7092bc772b7 |
RDF/XML JSON-LD Turtle |
ACDCConverter.p | Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used. | urn:uuid:9640bc4b-6569-4b49-aa1b-ec4b328ad2a4 |
RDF/XML JSON-LD Turtle |
VsConverter.droopCompensation | Compensation constant. Used to compensate for voltage drop when controlling voltage at a distant bus. The attribute shall be a positive value. | urn:uuid:0e2b2fd1-b0b6-456b-bce3-6d184e4c6c0f |
RDF/XML JSON-LD Turtle |
EquivalentInjection.regulationTarget | The target voltage for voltage regulation. The attribute shall be a positive value. | urn:uuid:9a20b105-8a42-4acc-935e-8311154bfd9e |
RDF/XML JSON-LD Turtle |
AsynchronousMachine.asynchronousMachineType | Indicates the type of Asynchronous Machine (motor or generator). | urn:uuid:05d8aacc-d337-4e90-a9ad-d77940aeda1c |
RDF/XML JSON-LD Turtle |
TapChanger.step | Tap changer position. Starting step for a steady state solution. Non integer values are allowed to support continuous tap variables. The reasons for continuous value are to support study cases where no discrete tap changer has yet been designed, a solution where a narrow voltage band forces the tap step to oscillate or to accommodate for a continuous solution as input. The attribute shall be equal to or greater than lowStep and equal to or less than highStep. | urn:uuid:c9a18791-9eba-422b-93c3-dff6996c2150 |
RDF/XML JSON-LD Turtle |
GeneratingUnit.normalPF | Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero. | urn:uuid:6bedee50-8963-400d-a633-6d07dedcb663 |
RDF/XML JSON-LD Turtle |
ControlArea.pTolerance | Active power net interchange tolerance. The attribute shall be a positive value or zero. | urn:uuid:4335c733-0cd6-4678-97e8-e787d6423aa0 |
RDF/XML JSON-LD Turtle |
EquivalentInjection.q | Equivalent reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions. | urn:uuid:1d9ef58e-e6a4-4c35-8627-38cc1b93c43b |
RDF/XML JSON-LD Turtle |
ApparentPowerLimit.value | The apparent power limit. The attribute shall be a positive value or zero. | urn:uuid:97abdf96-c89d-4bc0-ac0e-52c7ae190926 |
RDF/XML JSON-LD Turtle |
CsConverter.targetGamma | Target extinction angle. It is converter’s control variable used in power flow. It is only applicable for inverter if continuous tap changer control is used. Allowed values are within the range minGamma<=targetGamma<=maxGamma. The attribute shall be a positive value. | urn:uuid:7d6e849c-73db-445c-b5a9-be63afe4d9c0 |
RDF/XML JSON-LD Turtle |
TapChanger.controlEnabled | Specifies the regulation status of the equipment. True is regulating, false is not regulating. | urn:uuid:2da1baa3-f88a-4ab5-a257-f9e5d18b9849 |
RDF/XML JSON-LD Turtle |
EnergySource.reactivePower | High voltage source reactive injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions. | urn:uuid:56ad50ff-aa1a-4ab9-88f8-d9471d807780 |
RDF/XML JSON-LD Turtle |
ACDCConverter.q | Reactive power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used. | urn:uuid:8eb62849-edef-432c-be84-773644689210 |
RDF/XML JSON-LD Turtle |
RegulatingControl.enabled | The flag tells if regulation is enabled. | urn:uuid:638ab3f0-7421-49a0-a65a-1adce751432d |
RDF/XML JSON-LD Turtle |
RotatingMachine.p | Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. | urn:uuid:2e31b87d-57af-47d7-b4f2-f4b7f3d62b0c |
RDF/XML JSON-LD Turtle |
RegulatingCondEq.controlEnabled | Specifies the regulation status of the equipment. True is regulating, false is not regulating. | urn:uuid:df0f1ff8-71f8-4965-b4b3-f6971a9d6daa |
RDF/XML JSON-LD Turtle |
VoltageLimit.value | Limit on voltage. High or low limit nature of the limit depends upon the properties of the operational limit type. The attribute shall be a positive value or zero. | urn:uuid:d9f32796-a276-42b6-857f-173095c26f7b |
RDF/XML JSON-LD Turtle |
EnergyConsumer.p | Active power of the load. Load sign convention is used, i.e. positive sign means flow out from a node. For voltage dependent loads the value is at rated voltage. Starting value for a steady state solution. | urn:uuid:d9eaab4e-7792-4c7b-bd39-94b069e93c5e |
RDF/XML JSON-LD Turtle |
VsConverter.pPccControl | Kind of control of real power and/or DC voltage. | urn:uuid:80beba70-c2fb-4319-af0d-a81eeb668b1d |
RDF/XML JSON-LD Turtle |
ControlArea.netInterchange | The specified positive net interchange into the control area, i.e. positive sign means flow into the area. | urn:uuid:8a3152b1-4c59-4f74-b259-c9f607a84109 |
RDF/XML JSON-LD Turtle |
PowerElectronicsConnection.p | Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. | urn:uuid:1c277e1f-df16-4630-a94a-e196335e0111 |
RDF/XML JSON-LD Turtle |
VsConverter.targetQpcc | Reactive power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. | urn:uuid:898a03fc-43a6-4c11-aa73-e2d26ca1df0b |
RDF/XML JSON-LD Turtle |
ACDCTerminal.connected | The connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not. In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case. | urn:uuid:1bcbebe8-5d00-499e-b271-b19d1a46d2d1 |
RDF/XML JSON-LD Turtle |
VsConverter.qShare | Reactive power sharing factor among parallel converters on Uac control. The attribute shall be a positive value or zero. | urn:uuid:3b5255f8-15ad-4b85-bbe0-3e528bba4b87 |
RDF/XML JSON-LD Turtle |
RegulatingControl.minAllowedTargetValue | Minimum allowed target value (RegulatingControl.targetValue). | urn:uuid:67a4253a-1d1d-4a44-9fd4-a6f9c0bd0b24 |
RDF/XML JSON-LD Turtle |
Equipment.inService | Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model. | urn:uuid:67b777c0-a5b2-46ab-97bd-040c66b1d50f |
RDF/XML JSON-LD Turtle |
CsConverter.pPccControl | Kind of active power control. | urn:uuid:53242ae1-12a6-4790-9814-cd71c68a4d3e |
RDF/XML JSON-LD Turtle |
StaticVarCompensator.q | Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. | urn:uuid:80cfb71f-4383-4f65-aa08-1b17760bc414 |
RDF/XML JSON-LD Turtle |
EnergySource.voltageMagnitude | Phase-to-phase open circuit voltage magnitude used when voltage characteristics need to be imposed at the node associated with the terminal of the energy source, such as when voltages and angles from the transmission level are used as input to the distribution network. The attribute shall be a positive value or zero. | urn:uuid:0cddc7ac-49eb-4895-a198-0b3d924249ff |
RDF/XML JSON-LD Turtle |
VsConverter.targetPhasePcc | Phase target at AC side, at point of common coupling. The attribute shall be a positive value. | urn:uuid:25eaa42f-d3ee-4aeb-aa05-cd23c89d693b |
RDF/XML JSON-LD Turtle |
RegulatingControl.discrete | The regulation is performed in a discrete mode. This applies to equipment with discrete controls, e.g. tap changers and shunt compensators. | urn:uuid:4d7cd0e2-2375-41d1-8447-3256d5d2c860 |
RDF/XML JSON-LD Turtle |
SynchronousMachine.referencePriority | Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on. | urn:uuid:0e53e02b-a59a-4cdf-9826-35c56dd6c9ca |
RDF/XML JSON-LD Turtle |
EnergySource.voltageAngle | Phase angle of a-phase open circuit used when voltage characteristics need to be imposed at the node associated with the terminal of the energy source, such as when voltages and angles from the transmission level are used as input to the distribution network. The attribute shall be a positive value or zero. | urn:uuid:7e87693f-5b7e-440f-bad1-a05101c664bf |
RDF/XML JSON-LD Turtle |
ExternalNetworkInjection.q | Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions. | urn:uuid:a24cb554-a908-46a6-aa8c-0b2345522751 |
RDF/XML JSON-LD Turtle |
VsConverter.targetPowerFactorPcc | Power factor target at the AC side, at point of common coupling. The attribute shall be a positive value. | urn:uuid:d1a5fae7-a735-4556-b7af-c447aba7e545 |
RDF/XML JSON-LD Turtle |
BatteryUnit.storedE | Amount of energy currently stored. The attribute shall be a positive value or zero and lower than BatteryUnit.ratedE. | urn:uuid:da24ffb1-11bd-44a8-a17e-d1539e3b4f05 |
RDF/XML JSON-LD Turtle |
EnergySource.activePower | High voltage source active injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions. | urn:uuid:c7b65971-5dae-428f-bfe0-0615f769f3f8 |
RDF/XML JSON-LD Turtle |
EnergyConsumer.q | Reactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node. For voltage dependent loads the value is at rated voltage. Starting value for a steady state solution. | urn:uuid:edbfe75e-2ddb-48ae-b744-081e75f47848 |
RDF/XML JSON-LD Turtle |
CsConverter.targetIdc | DC current target value. It is converter’s control variable used in power flow. The attribute shall be a positive value. | urn:uuid:10b3b146-ba3d-4c1c-8402-0537808bcdce |
RDF/XML JSON-LD Turtle |
IdentifiedObject.mRID | Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. | urn:uuid:704202ac-974e-4576-a9e7-84581df72c59 |
RDF/XML JSON-LD Turtle |
RegulatingControl.targetValueUnitMultiplier | Specify the multiplier for used for the targetValue. | urn:uuid:7c03952f-fc7b-44d6-a6ff-ec5cef2f99a9 |
RDF/XML JSON-LD Turtle |
PowerElectronicsConnection.q | Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. | urn:uuid:fbcf4f0e-ecf7-4602-a6db-41c9358def79 |
RDF/XML JSON-LD Turtle |
CsConverter.operatingMode | Indicates whether the DC pole is operating as an inverter or as a rectifier. It is converter’s control variable used in power flow. | urn:uuid:005d38b3-85bd-4430-a3af-f179787235b7 |
RDF/XML JSON-LD Turtle |
ActivePowerLimit.value | Value of active power limit. The attribute shall be a positive value or zero. | urn:uuid:38399bbe-ff1d-4c54-ba4c-a8b25379a481 |
RDF/XML JSON-LD Turtle |
TCSCController.mode | Mode of the TCSC controller. | urn:uuid:92f60407-e16c-40a1-b30c-fe2ca63391b8 |
RDF/XML JSON-LD Turtle |
RemedialActionDependency.enabled | If true, the remedial action dependency is enabled, otherwise it is disabled. | urn:uuid:7bf769ab-fa28-40a5-9f06-e961e6b94e4c |
RDF/XML JSON-LD Turtle |
RemedialActionGroup.maxRegulatingUp | Maximum net amount of active power that the group of remedial actions can regulate up. | urn:uuid:026d19eb-9b13-45d6-bf44-862276b80045 |
RDF/XML JSON-LD Turtle |
PowerRemedialAction.maxRegulatingUp | Maximum net amount of active power that the remedial action can regulate up. | urn:uuid:e4834fe8-beb6-4593-8308-1f3c2952ac94 |
RDF/XML JSON-LD Turtle |
BiddingZone.maxInterchange | Maximum total active power (AC and DC) that the net position for the bidding zone can have to maintain operational security. Positive sign means flow into the bidding zone. | urn:uuid:40cdc3e4-0c31-4af4-a939-ade7a172c108 |
RDF/XML JSON-LD Turtle |
CompensatorController.mode | Mode of the compensator controller. | urn:uuid:8709af80-c90e-4e4d-924a-e5a2944075bc |
RDF/XML JSON-LD Turtle |
PhaseControlFunction.targetValue | Target value for the phase that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:21d977fd-a936-4102-a994-7d26cb35ede0 |
RDF/XML JSON-LD Turtle |
EnergyConsumer.participationFactor | Participation factor describing the entity part of the active power provided by a collection of entities (e.g. an active power forecast to a collection of entities is divided to each of the member entity according to the participation factor). Must be a positive value. In the case of a sharing strategy, the distribution is following entities value (V) equals aggregated value (T) divided by sum of participation factors (PF), i.e. V=T/sum(PF). In the case of priority strategy, the item with the lowest number gets allocated energy first. | urn:uuid:4ee14866-0602-49f4-9e7f-0e104f1ad512 |
RDF/XML JSON-LD Turtle |
AssessedElement.scannedThresholdMargin | Threshold percentage that a scanned element can be overloaded, on a given element, on top of any overload prior to optimisation (default= 5%). e.g. Initial loading of the element is 110%, with a 5% scanned threshold margin, the new maximum is 115% of the limit (e.g. PATL, TATL, etc). The allowed value range is [0,100]. | urn:uuid:9ad1b962-8d49-4676-9ab7-ab3b0c23f6ac |
RDF/XML JSON-LD Turtle |
BiddingZoneBorder.transmissionReliabilityMargin | Transmission Reliability Margin (TRM) is the minimum reserve that system operators must have available at their connections so that they can help other countries to which their system is directly or indirectly connected, if necessary. | urn:uuid:db3ad539-d0bc-4626-9e3a-671bfe4c3aca |
RDF/XML JSON-LD Turtle |
BiddingZone.regulatingUpAllocation | The balancing capacity allocated for regulating up, by increasing the production, decreasing the direct current export, increasing direct current import or reducing the consumption of energy in the bidding zone. This must be a positive number. | urn:uuid:bf2d4878-9048-4512-837f-e6a8a601f106 |
RDF/XML JSON-LD Turtle |
DCTieCorridor.q | Reactive power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used. | urn:uuid:e7840ed4-1c97-4bce-a484-23db8b6619b8 |
RDF/XML JSON-LD Turtle |
CurrentDroopOverride.enabled | True, if the current droop override is enabled (active). Otherwise false. | urn:uuid:f570a88b-6885-4d4b-a644-053161100784 |
RDF/XML JSON-LD Turtle |
GridStateAlteration.participationFactor | Participation factor describing the entity part of the active power provided by a collection of entities (e.g. an active power forecast to a collection of entities is divided to each of the member entity according to the participation factor). Must be a positive value. In the case of a sharing strategy, the distribution is following entities value (V) equals aggregated value (T) divided by sum of participation factors (PF), i.e. V=T/sum(PF). In the case of priority strategy, the item with the lowest number gets allocated energy first. e.g. If 0 this grid alteration does not participate. The sum of all participation factors for all grid state alterations associated with same remedial action shall be equal to 100%. | urn:uuid:f524a12b-cebd-4da0-ad3b-dd3498c098db |
RDF/XML JSON-LD Turtle |
RemedialAction.available | Identifies if the remedial action is available to be proposed. True means available, False means unavailable. | urn:uuid:b3b0769a-2264-4c35-b1bf-ed89a47af8ec |
RDF/XML JSON-LD Turtle |
BiddingZoneBorder.availableTransferCapacity | Available Transfer Capacity (ATC) means the transmission capacity that remains available, after allocation procedure, to be used under the physical conditions of the transmission system. ATC value is defined as: ATC = NTC - AAC. | urn:uuid:f658578d-0662-4954-ade8-6c6058d9b94d |
RDF/XML JSON-LD Turtle |
ContingencyWithRemedialAction.enabled | If true, the contingency with remedial action is enabled, otherwise it is disabled. | urn:uuid:bdab74e1-6b78-4770-98f6-82c8991da60b |
RDF/XML JSON-LD Turtle |
DirectCurrentController.mode | Mode of the dc controller. | urn:uuid:1c2e0f58-aa25-43b0-addd-593b9a8e45f9 |
RDF/XML JSON-LD Turtle |
CircuitShare.contributionFactor | Contribution factor for the circuit which is part of a power transfer corridor. The allowed value range is [0,100]. | urn:uuid:fa3b5fd8-d4a2-421d-a192-7eaf65ec8f4a |
RDF/XML JSON-LD Turtle |
BiddingZone.netACInterchangeTolerance | The area AC Net Position tolerance. | urn:uuid:8b0f1899-a7f2-48df-bc20-edc8376280f6 |
RDF/XML JSON-LD Turtle |
EnergyGroup.participationFactor | Participation factor. | urn:uuid:6da574b8-87df-483a-8570-d48375de2269 |
RDF/XML JSON-LD Turtle |
DCPole.minEconomicP | Low economic active power limit that shall be greater than or equal to the minimum operating active power limit. | urn:uuid:44264880-13fc-4a8e-ba4f-3b2814d95039 |
RDF/XML JSON-LD Turtle |
FuelStorage.energyStorage | Amount of energy available in the storage. | urn:uuid:5f56ae88-d0ca-474a-b2e3-102c6f4fa7b2 |
RDF/XML JSON-LD Turtle |
CurrentDroopControlFunction.targetValueCapacitive | Setpoint when control is active in capacitive region. | urn:uuid:e5f02e60-e2ba-4b56-a64c-3f277adf8108 |
RDF/XML JSON-LD Turtle |
ReactivePowerControlFunction.targetValue | Target value for the reactive power that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:cb1e5b0f-d875-4b5b-b7b0-7f1d72b4a608 |
RDF/XML JSON-LD Turtle |
BiddingZone.minInterchange | Minimum total active power (AC and DC) that the net position for the bidding zone can have to maintain operational security. Negative sign means flow out of the bidding zone. | urn:uuid:b55d3198-6d5b-46eb-8e87-bf3048820d7b |
RDF/XML JSON-LD Turtle |
EnergyBlockOrder.participationFactor | Participation factor. | urn:uuid:34ec7ba2-fd87-45d1-9465-5e43d449f758 |
RDF/XML JSON-LD Turtle |
GridStateAlteration.enabled | The status of the GridStateAlteration set by an operation or by a signal resulting from a control action. | urn:uuid:62e43d79-7a35-42be-ab09-5e5fd0058588 |
RDF/XML JSON-LD Turtle |
Contingency.probability | The forecasted probability of the occurrence of the contingency based on the given operational condition, status of the equipment and the forecasted environment condition. The allowed value range is [0,100]. | urn:uuid:2760d502-0050-4e13-aab0-4afd74435e2a |
RDF/XML JSON-LD Turtle |
CurrentControlFunction.targetValue | Target value for the current that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:ddd88d82-cdd4-4ce9-a5fc-3e758e03d56e |
RDF/XML JSON-LD Turtle |
CurrentDroopOverride.targetValueInductive | Setpoint when control is active in inductive region. | urn:uuid:82d1c3da-e543-4bed-aac3-364022fcac79 |
RDF/XML JSON-LD Turtle |
DCTieCorridor.p | Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used. | urn:uuid:63887b20-32a7-4991-b770-75638a5c602d |
RDF/XML JSON-LD Turtle |
VoltageControlFunction.targetValue | Target value for the voltage that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:2c954d38-ed51-4f75-8aa3-afd5b6f82476 |
RDF/XML JSON-LD Turtle |
ScheduleResource.participationFactor | Participation factor describing the entity part of the active power provided by a collection of entities (e.g. an active power forecast to a collection of entities is divided to each of the member entity according to the participation factor). Must be a positive value. In the case of a sharing strategy, the distribution is following entities value (V) equals aggregated value (T) divided by sum of participation factors (PF), i.e. V=T/sum(PF). In the case of priority strategy, the item with the lowest number gets allocated energy first. | urn:uuid:6f0b364e-a28c-4c29-bd40-9692dc5f4b09 |
RDF/XML JSON-LD Turtle |
Equipment.networkAnalysisEnabled | The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true. | urn:uuid:ee8bd1ad-fb29-4fee-bdad-da96b34311a9 |
RDF/XML JSON-LD Turtle |
BiddingZoneBorder.netTransferCapacity | Net Transfer Capacity (NTC) is defined as NTC = TTC – TRM and corresponds to the maximum exchange between two areas compatible with operational security limits applicable in both areas and taking into account the technical uncertainties on future network conditions. | urn:uuid:f37d76b6-0fa6-4476-a12b-940da800e5e6 |
RDF/XML JSON-LD Turtle |
BiddingZoneBorder.alreadyAllocatedFlow | The maximum allowed flow on the collection of interconnection between two bidding zones. | urn:uuid:294db562-b036-4d68-8c4d-df6df80fd825 |
RDF/XML JSON-LD Turtle |
BiddingZone.regulatingDownAllocation | The balancing capacity allocated for regulating down, by decreasing the production, increasing the direct current export, decreasing direct current import or increasing the consumption of energy in the bidding zone. This must be a positive number. | urn:uuid:77b59f59-5d41-4f9f-82fe-dd6cd9f43e30 |
RDF/XML JSON-LD Turtle |
AssessedElement.enabled | If true, the assessed element is enabled, otherwise it is disabled. | urn:uuid:85982b36-c98e-4e28-958b-4c6da6651a90 |
RDF/XML JSON-LD Turtle |
CurrentDroopControlFunction.targetValueInductive | Setpoint when control is active in inductive region. | urn:uuid:b28400fb-56f8-49fb-9f98-b7b4b0e94cf2 |
RDF/XML JSON-LD Turtle |
GeneratingUnit.participationFactor | Participation factor describing the entity part of the active power provided by a collection of entities (e.g. an active power forecast to a collection of entities is divided to each of the member entity according to the participation factor). Must be a positive value. In the case of a sharing strategy, the distribution is following entities value (V) equals aggregated value (T) divided by sum of participation factors (PF), i.e. V=T/sum(PF). In the case of priority strategy, the item with the lowest number gets allocated energy first. | urn:uuid:af53eab1-df22-4a32-bcbf-df4fb9767f80 |
RDF/XML JSON-LD Turtle |
FACTSEquipment.q | Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. | urn:uuid:209a41cc-aebd-4ab4-91ee-e066e213a889 |
RDF/XML JSON-LD Turtle |
VoltageInjectionControlFunction.targetValue | Target value for the voltage that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:e9712674-a06f-4b09-895e-76c8df4ed6dd |
RDF/XML JSON-LD Turtle |
SubstationController.mode | Mode of the substation controller. | urn:uuid:4c6b4a0c-41d0-4ba8-91c0-974cf2dc6c46 |
RDF/XML JSON-LD Turtle |
InjectionController.mode | Mode of the injection controller. | urn:uuid:cc41f3b7-4412-45db-9e7f-675561ba1fc7 |
RDF/XML JSON-LD Turtle |
BiddingZone.netPosition | Net position is the netted sum of electricity exports and imports for each market time unit for a bidding zone. | urn:uuid:9eba210e-c91f-4d8d-b409-6a62c695854d |
RDF/XML JSON-LD Turtle |
AssessedElement.maxMarginAdjustment | Maximum adjustment, relative to maximum flow allowed for exceeding the maximum flow of this assessed element. The allowed value range is [0,100]. | urn:uuid:93b96ef2-a8fe-4576-b601-d2888f422267 |
RDF/XML JSON-LD Turtle |
PowerTransferCorridor.enabled | It enables/disables the monitoring/assessment of a power transfer corridor. True means that the monitoring of the power transfer corridor is assessed. False means the power transfer corridor is not assessed. | urn:uuid:0293d08f-20b8-48c7-942e-fbad5ede506e |
RDF/XML JSON-LD Turtle |
ThyristorControlledSeriesCompensator.compensationImpedance | The actual compensation impedance provided by the compensator. The attribute value shall be positive if compensation is in the capacitive range. The attribute value shall be negative if compensation is in the inductive rating. | urn:uuid:71681a70-896b-4855-9ba1-de6a3e617eb4 |
RDF/XML JSON-LD Turtle |
VoltageAngleLimit.value | The difference in angle degrees between referenced by the association end OperationalLimitSet.Terminal and the Terminal referenced by the association end VoltageAngleLimit.AngleReferenceTerminal. The value shall be positive (greater than zero). | urn:uuid:9eb2dc49-0ca2-4e36-9e74-ee0c94b012fe |
RDF/XML JSON-LD Turtle |
RemedialActionScheme.armed | Defines the arming status of the remedial action scheme. It is set by operation or by signal. | urn:uuid:dc42fd13-4b74-469e-886c-e3c0cffc9ff7 |
RDF/XML JSON-LD Turtle |
RegulatingCondEq.controlEnabled | Specifies the regulation status of the equipment. True is regulating, false is not regulating. | urn:uuid:e171117b-df36-4bd5-bce4-2d7974a891c2 |
RDF/XML JSON-LD Turtle |
InfeedLimit.valueA | Value of current limit. The attribute shall be a positive value or zero. | urn:uuid:5ab8977f-a45d-4f58-8341-757d585ae670 |
RDF/XML JSON-LD Turtle |
RangeConstraint.value | The value at the time. The meaning of the value is defined by the attribute referenced by the PropertyReference. The value can be integer, float or boolean. In case of boolean 1 equals true and 0 equals false. If the valueKind is incremental or incrementalPercentage, then the value shall be positive (greater than zero). If the valueKind is incrementalPercentage, then the value shall be in the range [0, 100]. | urn:uuid:970974fd-1205-4186-aa2b-4162b97da428 |
RDF/XML JSON-LD Turtle |
BiddingZoneBorder.totalTransferCapacity | Total Transfer Capacity (TTC) is the maximum exchange program between two areas compatible with operational security standards applicable at each system if future network conditions, generation and load patterns were perfectly known in advance. | urn:uuid:57545b31-1dc8-4ed3-bbaf-990d9a1228e6 |
RDF/XML JSON-LD Turtle |
HydroPump.participationFactor | Participation factor describing the entity part of the active power provided by a collection of entities (e.g. an active power forecast to a collection of entities is divided to each of the member entity according to the participation factor). Must be a positive value. In the case of a sharing strategy, the distribution is following entities value (V) equals aggregated value (T) divided by sum of participation factors (PF), i.e. V=T/sum(PF). In the case of priority strategy, the item with the lowest number gets allocated energy first. | urn:uuid:6af6a7c6-b840-422e-a25a-ec8cdf1ab254 |
RDF/XML JSON-LD Turtle |
FunctionBlock.enabled | True, if the function block is enabled (active). Otherwise false. | urn:uuid:e9fe1ee9-241d-48df-8939-6aa9430a73b1 |
RDF/XML JSON-LD Turtle |
DCSwitch.open | The attribute tells if the switch is considered open when used as input to topology processing. | urn:uuid:e0bf863f-07e7-41b8-9f31-86fc441d756b |
RDF/XML JSON-LD Turtle |
BiddingZone.minImportP | Minimum imported active power requirement. | urn:uuid:823eefcc-df69-49ce-972d-cf0be58bcd81 |
RDF/XML JSON-LD Turtle |
ThyristorControlledSeriesCompensator.currentSectionNumber | The current section on which the TCSC is operating. | urn:uuid:1dd04f5f-eb85-489d-97c4-3d95de3a83c1 |
RDF/XML JSON-LD Turtle |
SSSCController.mode | Mode of the Static Synchronous Series compensator controller. | urn:uuid:1a266e01-7291-47fe-8c46-60fb62be250f |
RDF/XML JSON-LD Turtle |
BiddingZone.netACInterchange | The netted aggregation of all AC external schedules of an area. Positive sign means flow into the area (Import). | urn:uuid:a3874978-d2c3-44bd-9367-fa8a1cb40a5c |
RDF/XML JSON-LD Turtle |
PowerRemedialAction.maxRegulatingDown | Maximum net amount of active power that the remedial action can regulate down. | urn:uuid:dd5c8924-e090-4554-9fb4-5b08cf76db46 |
RDF/XML JSON-LD Turtle |
DCVoltageControlFunction.targetValue | Target value for the voltage that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:317ec706-2384-41a8-8b9a-a665053c35df |
RDF/XML JSON-LD Turtle |
Equipment.inService | Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model. | urn:uuid:126623ad-2c0d-4c1c-a573-a04d017c1529 |
RDF/XML JSON-LD Turtle |
RemedialActionGroup.maxRegulatingDown | Maximum net amount of active power that the group of remedial actions can regulate down. | urn:uuid:f7200a2e-0c04-44e9-9155-f4f7fcad9114 |
RDF/XML JSON-LD Turtle |
PowerFactorControlFunction.targetValue | Target value for the power factor that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:4434b99a-027e-4655-b63b-a0187785e16d |
RDF/XML JSON-LD Turtle |
DCCurrentControlFunction.targetValue | Target value for the current that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:62b0ec75-38a4-43af-8d35-412899b78fda |
RDF/XML JSON-LD Turtle |
InfeedLimit.valueW | Value of active power limit. The attribute shall be a positive value or zero. | urn:uuid:a680a1dd-d4d9-4ac5-b6ff-bcb955f1a2e0 |
RDF/XML JSON-LD Turtle |
AssessedElementWithContingency.enabled | If true, the assessed element with contingency is enabled, otherwise it is disabled. | urn:uuid:00c1d3f5-1955-4022-a423-cb0a38b374e6 |
RDF/XML JSON-LD Turtle |
StageTrigger.armed | The status of the class set by operation or by signal. Optional field that will override other status fields. | urn:uuid:1ee64ce1-6a2c-4a19-b34d-ab4c718bad4f |
RDF/XML JSON-LD Turtle |
BiddingZone.netDCInterchange | The netted aggregation of all DC external schedules of an area. Positive sign means flow into the area. | urn:uuid:0ebb40b5-b27e-4f7b-b295-94a299f59068 |
RDF/XML JSON-LD Turtle |
DCPole.maxEconomicP | Maximum high economic active power limit, that should not exceed the maximum operating active power limit. | urn:uuid:564df47f-8a07-49f5-a089-d82d06b5c4fb |
RDF/XML JSON-LD Turtle |
PTCActivePowerSupport.value | The support that a System Integrity Protection Scheme (SIPS) gives to a Power Transfer Corridor (PTC). | urn:uuid:24303e9c-8bb0-46d6-b182-56a7bf2ba0d8 |
RDF/XML JSON-LD Turtle |
CurrentDroopOverride.targetValueCapacitive | Setpoint when control is active in capacitive region. | urn:uuid:c35ed0fc-67e0-4275-991d-47e63f1e976a |
RDF/XML JSON-LD Turtle |
AssessedElementWithRemedialAction.enabled | If true, the assessed element with remedial action is enabled, otherwise it is disabled. | urn:uuid:4aeb763c-824b-4aa4-96ec-5e97b0997c10 |
RDF/XML JSON-LD Turtle |
BiddingZoneBorder.alreadyAllocatedCapacity | Already Allocated Capacity (AAC) means the total amount of allocated transmission rights i.e. transmission capacity reserved by virtue of historical long-term contracts and the previously held transmission capacity reservation auctions. | urn:uuid:278e7131-2c07-4505-8175-639fb65347cb |
RDF/XML JSON-LD Turtle |
PowerElectronicsUnit.participationFactor | Participation factor describing the entity part of the active power provided by a collection of entities (e.g. an active power forecast to a collection of entities is divided to each of the member entity according to the participation factor). Must be a positive value. In the case of a sharing strategy, the distribution is following entities value (V) equals aggregated value (T) divided by sum of participation factors (PF), i.e. V=T/sum(PF). In the case of priority strategy, the item with the lowest number gets allocated energy first. | urn:uuid:4da10084-f2d2-40ed-80fa-e80e0a0c7f15 |
RDF/XML JSON-LD Turtle |
ImpedanceControlFunction.targetValue | Target value for the impedance that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:b4093159-7731-4d49-9c90-caa4234ef0e5 |
RDF/XML JSON-LD Turtle |
DCPole.longPF | Energy consumer long term economic participation factor. | urn:uuid:46946677-01a9-4f58-8666-14b65dd05267 |
RDF/XML JSON-LD Turtle |
Contingency.mustStudy | Set true if must study this contingency. | urn:uuid:e6a79d11-ab88-4887-8e98-9a21a146b97b |
RDF/XML JSON-LD Turtle |
RemedialActionScheme.inService | Specifies the availability of the Remedial Action Scheme (RAS). If true, the RAS is available for contingency processing. If false, the RAS is treated by contingency processing as if it is not in the model. | urn:uuid:5ff26ccf-49f4-493f-9425-74d7d969c13a |
RDF/XML JSON-LD Turtle |
DCPole.shortPF | Energy consumer short term economic participation factor. | urn:uuid:2c472fdd-1cba-47b8-b0f5-083e39448cd2 |
RDF/XML JSON-LD Turtle |
ActivePowerControlFunction.targetValue | Target value for the active power that the control function is calculating to achieve by adjusting the operational setting to the controlled equipment. | urn:uuid:2e610aa2-15d7-4d61-b1a9-b727eae71171 |
RDF/XML JSON-LD Turtle |
AssessedElement.maxFlow | Maximum flow on a conducting equipment or a collection of conducting equipment forming a power transfer corridor. For assessed element that becomes critical due to contingency, this value represents the maximum flow with remedial action taken into consideration. | urn:uuid:b96e7fab-4784-41f0-8e7e-e1cf76a57a99 |
RDF/XML JSON-LD Turtle |
AreaDispatchableUnit.enabled | Identifies if the unit is enabled to accept a dispatch instruction. If true, the unit is enabled to accept a dispatch instruction. If false, the unit has the capability, but it is not enabled to receive a dispatch instruction. | urn:uuid:b7e0f30f-765f-4d19-81f1-d8db63332a2a |
RDF/XML JSON-LD Turtle |
RotatingMachineController.mode | Mode of the rotating machine controller. | urn:uuid:df965405-0317-4366-9467-6fa9ced80447 |
RDF/XML JSON-LD Turtle |
DCSwitch.locked | If true, the switch is locked. The resulting switch state is a combination of locked and DCSwitch.open attributes as follows:
|
urn:uuid:bb033823-deaa-4dc1-910f-4ecf4ceb1254 |
RDF/XML JSON-LD Turtle |
Reservoir.energyStorage | Amount of energy available in the storage. | urn:uuid:ea6d30c2-25d2-46e8-877c-7f04a91b8b95 |
RDF/XML JSON-LD Turtle |
AssessedElement.positiveVirtualMargin | A positive margin that defines the overload allowed in a solution for the assessed element for the current situation. The margin represents influences that can be solved by the System Operators using available remedial action which is not cross-border relevant remedial action. All relevant operational limits (e.g. PATL, TATL, etc) are modified by this margin value. The attribute represents the increase. The allowed value range is [0,100]. | urn:uuid:fa6d378d-b9f3-471a-a7b8-ee5a16aad4ae |
RDF/XML JSON-LD Turtle |